February 17, 2025
Control valve selection should be based on the site to provide the medium, flow, valve issued after the pressure, temperature, viscosity, process pipe diameter and other parameters, after the original manufacturer of the original software calculations, and fully comply with the design requirements.
The starting actuator should be installed in a place where the ambient temperature is not higher than +60℃ and not lower than -40℃, and should be far away from the equipment with high vibration. In order to avoid heat aging of the diaphragm, the distance between the upper diaphragm cover of the control valve and the heat-carrying pipeline or equipment should be more than 200mm. When the nominal diameter of the valve is different from that of the pipeline, a piece of reducer should be added between the two. The pneumatic actuator should be installed vertically on the horizontal pipeline.
When special circumstances require horizontal or inclined installation, except for small-diameter valves, support should generally be added. Even if the valve is installed upright, it should be supported when it has a large self-weight and vibration.
The direction of the fluid through the control valve is marked on the valve body, and cannot be installed in reverse, just as the orifice plate cannot be installed in reverse.
Control valve before and after the installation of a cut-off valve, in order to repair the control valve removed.
Before the control valve is installed, the piping should be cleaned to remove dirt and weld slag. After installation, the pipeline and valve should also be cleaned again, and check the sealing performance of the valve and pipeline connections. When the medium is initially energized, the valve should be kept in the fully open position to avoid magazine jamming.