Specifications
Input Signal: Electric
Data Interface: Wired
Supply Media: Non Corrosive Gas
Process Control: Flow, Pressure, Temperature, Level
Position Control: Throttling Control, On/Off
Max Outlet Pressure: 145 Psig
Diagnostics: Yes
Communication Protocol: 4-20 MA HART
Highlight:

Fisher DVC6205 digital valve positioner

,

HART protocol valve controller

,

split pneumatic control valve

Basic Infomation
Brand Name: Fisher
Model Number: DVC6205 DVC6215
Payment & Shipping Terms
Packaging Details: Hard cardboard box + protection
Delivery Time: 45-60 work days
Payment Terms: T/T
Supply Ability: 1000 units per year
Product Description
Fisher DVC6205/DVC6215 Split Digital Valve Positioners
Product Overview

The Fisher DVC6205 and DVC6215 are advanced split-type digital valve positioners designed for precise pneumatic control in industrial automation. As part of Emerson's FIELDVUE series, these smart devices integrate HART and FOUNDATION Fieldbus communication protocols, enabling real-time diagnostics and adaptive tuning.

The DVC6205 (base unit) and DVC6215 (remote travel sensor) form a modular system, ideal for applications requiring non-contact feedback or remote mounting. With explosion-proof certifications and robust construction, they ensure reliable performance in harsh environments.

Product Attributes
Input Signal Electric
Data Interface Wired
Supply Media Non Corrosive Gas
Process Control Flow, Pressure, Temperature, Level
Position Control Throttling Control, On/Off
Max Outlet Pressure 145 psig
Diagnostics Yes
Communication Protocol 4-20 mA HART
Technical Parameters
Parameter DVC6205 DVC6215
Control Type Pneumatic Pneumatic
Input Signal 4-20mA + HART/FF 4-20mA + HART/FF
Accuracy ±1% (Integral) / ±2% (Remote) ±1% (Integral) / ±2% (Remote)
Output Pressure 0.2-6 bar / 0.1-10 bar 0.2-6 bar / 0.1-10 bar
Stroke Range 8-250mm (Linear) / 24-100° (Rotary) N/A (Feedback Sensor)
Communication HART 7/FOUNDATION Fieldbus HART 7/FOUNDATION Fieldbus
Protection Class IP66 IP66
Operating Temp -40°C to +85°C -40°C to +85°C
Material Aluminum/Stainless Steel Aluminum/Stainless Steel
Certifications ATEX/IECEx/NEPSI ATEX/IECEx/NEPSI
Key Features
  • Modular Split Design: DVC6205 (base) and DVC6215 (sensor) enable flexible remote mounting.
  • High Precision: ±1% accuracy for integral setups, ±2% for remote configurations.
  • Smart Diagnostics: FIELDVUE technology monitors valve health and optimizes performance.
  • Harsh Environment Resistance: IP66 rating and wide temperature range (-40°C to +85°C).
  • Multi-Protocol Support: Compatible with HART, FOUNDATION Fieldbus, and PROFIBUS.
  • Safety Compliance: ATEX/IECEx certifications for explosive atmospheres.
Applications
  • Oil & Gas: Control valves in pipelines, refineries, and offshore platforms.
  • Chemical Processing: Precise regulation of corrosive or volatile fluids.
  • Power Generation: Steam turbine control and boiler feedwater systems.
  • Pharmaceuticals: Sterile environment valve automation.
  • Water Treatment: Pump stations and wastewater processing.