The SQ 05.2 – 14.2 (open-close) and SQR 05.2 – 14.2 (modulating) from AUMA are electric part-turn actuators certified under UKCA for incorporation into valve machinery. Driven by 3-phase AC motors with self-locking gearing, they provide adjustable torque for 90° operations. Paired with controls like AUMA NORM, SEMIPACT, MATIC, or AUMATIC AC 01.2, they support advanced features including fieldbus integration. These actuators ensure compliance with UK safety standards (Machinery, Electrical, EMC, RoHS, Radio), making them reliable for industrial valve automation.
| Parameter | Details |
|---|---|
| Type of Duty | SQ: S2 - 15/30 min; SQR: S4 - 25/50%, S5 - 25% |
| Torque Range | 50-2,500 Nm (SQ), Modulating 75-1,200 Nm (SQR) |
| Swing Angle | 75°-105° (adjustable); Multi-revolution options up to 10 turns |
| Operating Time (90°) | SQ: 4-100 s; SQR: 8-100 s |
| Starts per Hour | SQR: Max 1,500 c/h |
| Motor Voltage | 100-690 V AC, 50/60 Hz; Tolerance ±10/30% voltage, ±5% frequency |
| Current Draw | 200-1,200 mA (voltage-dependent) |
| Ambient Conditions | -25°C to +70/60°C; ≤2,000 m altitude; 100% RH |
| Enclosure | IP68 (8 m/96 h); Pollution degree 4 |
| Vibration | 1 g, 10-200 Hz |
| Corrosion | KS (C4 moderate); KX (C5 extreme) |
| Inputs/Outputs | Control: 7-15 mA; Contacts: 250 V AC, 1-5 A; Analogue: 0/4-20 mA (500 Ω load) |
| Standards Compliance | EN 60034-1, EN 50178, EN IEC 63000, EN 61000-6-2/4, EN 300 328, EN 301 489 |
Engineered for part-turn valve actuation in non-hazardous industrial settings, including water/power plants and chemical processes. SQ for on-off duties in pipelines; SQR for precise modulating in flow control systems. Optional Ex zone 22 for dust areas; complies with EN 15714-2 lifetime standards.
What power variations are supported?
Wide range 100-690 V AC with tolerances; optional 24 V DC for controls.
How does it handle wrong phase sequence?
Automatic correction prevents incorrect rotation.
Is it suitable for modulating applications?
Yes, SQR models with S4/S5 duty and adaptive dead band.
What documentation is available?
Technical docs per Annex VII B; request via national authorities.
Can it be used above 2,000 m altitude?
Standard up to 2,000 m; consult AUMA for higher elevations.