Product Overview
The Fisher DVC6200 is a digital valve controller that communicates via HART protocol. It takes a two-wire 4-20 mA signal and converts it to a pneumatic pressure output to drive a valve actuator. The unit is designed as a drop-in replacement for analog positioners on most pneumatic actuators. A non-contact, linkage-free position feedback system removes all rubbing parts, which dramatically extends cycle life. The fully potted electronics stand up to vibration, temperature fluctuations, and aggressive plant air.
Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | Fisher |
| Communication Protocol | 4-20 mA HART |
| Input Signal | Electric |
| Data Interface | Wired |
| Diagnostics | Yes |
| Max Outlet Pressure | 145 psig |
| Mounting Type | Integral Mounted |
| Operating Temperature | Standard Temperature, High Temperature |
| Position Control | Throttling Control, On/Off |
| Power Source | Local |
| Process Control | Flow, Pressure, Temperature, Level |
| Supply Media | Air, Natural Gas, Nitrogen |
| Area Classification | Explosion Proof, Intrinsically Safe, FISCO, Type N, Flame Proof, Non-incendive for FM |
| Certifications | CSA, FM, ATEX, IECEx, CUTR, Peso, KGS, INMETRO, NEPSI, TIIS, Natural Gas Certified, Single Seal Device; Marine Approvals: Lloyd‘s Register, Bureau Veritas, DNV, ABS |
| Actuator Compatibility (Linear) | Sliding-stem linear actuators with rated travel between 6.35 mm / 0.25 in. and 606 mm / 23.375 in. |
| Actuator Compatibility (Rotary) | Quarter-turn rotary actuators with rated travel between 45° and 180° |
| Housing Material | A03600 low copper aluminum alloy (standard); stainless steel (optional) |
| Elastomers | Nitrile (standard); Fluorosilicone (extreme temperature) |
| Weight (DVC6200 Aluminum) | 3.5 kg / 7.7 lbs |
| Weight (DVC6200 Stainless Steel) | 8.6 kg / 19 lbs |
| Weight (DVC6205) | 4.1 kg / 9 lbs |
| Weight (DVC6215) | 1.4 kg / 3.1 lbs |
| Minimum Terminal Voltage | 9.5 VDC for analog control; 10 VDC for HART communication |
Application Industry
The DVC6200 is widely applied in refining, chemical, nuclear, oil and gas, power generation, pulp and paper, food and beverage, water and wastewater, pharmaceutical, and metals and mining. It handles flow, pressure, temperature, and level control loops.
Common Problems
No communication: verify power supply, terminal voltage (9–32 VDC), and wiring on the printed wiring board.
Valve does not fully stroke: check pneumatic tubing and supply pressure; confirm the function block is in the correct mode.
I/P converter output out of specification: possible defective module base seal, relay, or 67CFR regulator.
Replacement Models
The DVC6200 retrofits existing analog positioner installations and is a common upgrade from the DVC2000. For other brands, confirm mounting, travel, and protocol compatibility before ordering.
Overall Rating
Rating Snapshot
The following is the distribution of all ratingsAll Reviews