Product Overview
The Fisher DVC2000 is a compact digital valve controller built with a microprocessor and HART communication. It takes a 4-20 mA input and produces a pneumatic output to operate a single-acting actuator. Mounting directly to the actuator yoke keeps installation simple.
The feedback system is linkage-less and magnetic, so no components rub together and cycle life is extended. A local interface with a multilingual LCD allows configuration, calibration, and tuning right at the valve. The two-stage design responds quickly to small input changes for tighter process control. The instrument self-diagnoses continuously; if a fault appears, an alert symbol shows on the screen.
Technical Specifications
| Parameter | Specification |
|---|---|
| Brand | Fisher |
| Communication Protocol | HART, 4-20mA Analog |
| Input Signal | Electric |
| Data Interface | Wired |
| Diagnostics | Yes |
| Max Outlet Pressure | 101 psig |
| Mounting Type | Integral Mounted |
| Operating Temperature | Standard Temperature, High Temperature |
| Position Control | Throttling Control, On/Off |
| Power Source | Local |
| Process Control | Flow, Pressure, Temperature, Level |
| Supply Media | Air, Non Corrosive Gas |
| Area Classification | Intrinsically Safe, Non-incendive for CSA and FM |
| Certifications | CSA, FM, ATEX, IECEx, CUTR, PED, UL, Peso, KGS, INMETRO, NEPSI, ANZEx |
| Weight | 1.5 kg / 3.3 lbs |
| Housing Material | Aluminum construction |
| Maximum Travel | 606 mm / 23-7/8 inches (single-acting pneumatic actuators) |
| Temperature Range | -40 to +80°C / -40 to +176°F |
| Maximum Inlet Pressure | 7 barg / 100 psig |
| Integral Mounting | Available on GX, 657, and 667 size i actuators |
Application Industry
The DVC2000 is used in chemical, oil and gas, refining, pulp and paper, power, food and beverage, and pharmaceutical plants. It controls flow, pressure, temperature, and level loops. Its compact size and simple setup suit standard control valves with short strokes and routine procedures.
Common Problems
Instrument will not communicate: Check available voltage. Confirm terminal voltage is within 9–32 VDC and inspect wiring connectors on the printed wiring board.
Flash ROM Fail: Restart the instrument. If the failure does not clear, replace the printed wiring board assembly.
Valve does not respond to control signals: Check pneumatic connections and supply pressure. Verify function block is in the correct mode.
Display shows alert symbol ⚠️: The DVC2000 self-diagnoses continuously. Check the alert record, which stores up to 20 alerts from Valve Alerts or Failure Alerts groups.
Replacement Models
The DVC2000 is a standard control valve positioner. The DVC6200 can directly replace the DVC2000 in many applications — same product line and compatible mounting. The DVC6200 offers advanced diagnostics and linkless feedback for critical control valves, while the DVC2000 remains a practical choice for routine applications. For cross-vendor alternatives, verify mounting, travel range, and communication protocol before ordering.