The SAMSON Type 3731-5 is an electropneumatic positioner for pneumatic control valves, designed for process automation systems using FOUNDATION Fieldbus communication.
Instead of receiving a conventional 4–20 mA setpoint, the 3731-5 receives its reference value through the fieldbus network and converts it into the pneumatic output pressure required by the actuator. It supports linear valve travel and rotary actuator movement.
The device includes integrated function blocks, including a PID controller, an analog output function block and a binary input function block. These functions allow selected control and monitoring tasks to be handled at the field level.
Automatic initialization, local menu operation and valve diagnostics help commissioning and routine maintenance.
Technical Specifications| Parameter | Specification |
|---|---|
| Product Type | Electropneumatic Positioner |
| Model | SAMSON 3731-5 |
| Communication | FOUNDATION Fieldbus |
| Transmission Technology | IEC 61158-2 |
| Rated Travel | 3.6–200 mm |
| Rotary Actuator Range | 24°–100° |
| Application | Pneumatic control valves |
| Function Blocks | PID, AO and one binary input function block |
| Initialization | Automatic initialization with selectable modes |
| Local Operation | LCD and menu-driven operation |
| Diagnostics | Integrated monitoring and diagnostic functions |
| Extended Diagnostics | EXPERTplus version |
| Mounting | Compatible linear and rotary actuator interfaces, depending on configuration |
The Type 3731-5 is a FOUNDATION Fieldbus version. Confirm the required fieldbus revision, approvals and mounting configuration against the device nameplate and project specifications.
Application IndustryOil and gas
Petrochemical processing
Chemical plants
Power stations
Refinery process units
Water treatment facilities
Other process automation installations using FOUNDATION Fieldbus
Fieldbus communication failureCheck the segment wiring, network configuration, device address and compatibility with the control system.
Incorrect valve travel or responseVerify the mechanical linkage, actuator movement and initialization settings. Reinitialization may be required after maintenance or changes to the valve assembly.
Insufficient actuator movementCheck the instrument air supply, pneumatic connections and actuator condition. The positioner must be matched to the actuator and valve assembly.
Diagnostic alarmsReview the device diagnostic messages and operating conditions before replacing the positioner. Mechanical valve problems can also affect positioner performance.
Replacement selection must take account of the communication system and valve assembly.
SAMSON Type 3731-5: same-model replacement, subject to configuration matching
SAMSON Type 3731-3: HART version; requires a control-system and communication review before substitution
SAMSON Type 3730 series: alternative positioner family for selected applications, subject to mounting, communication and approval checks
A HART positioner and a FOUNDATION Fieldbus positioner are not interchangeable on a like-for-like basis. Confirm the control system interface before ordering.
Why Buy From UsSourcing support for SAMSON positioners
Assistance identifying communication versions and type codes
Model checking against valve and actuator details
Support for industrial spare-part and project orders
International logistics coordination
We can review your existing nameplate and application information before confirming the proposed model.
Stock & Delivery TimeStock and lead time vary by model version, communication type and configuration. Please send the complete type designation and quantity for confirmation.
We can coordinate export packing and international shipment based on the destination and delivery requirements.
RFQ FormPlease include the following information in your inquiry:
Model: SAMSON 3731-5
Required Quantity
Complete Type Number
Communication Protocol: FOUNDATION Fieldbus
Valve / Actuator Model
Mounting Interface
Destination Country
Required Delivery Date
Other Technical Requirements
A clear nameplate photo is helpful when checking the exact configuration.
Overall Rating
Rating Snapshot
The following is the distribution of all ratingsAll Reviews