A control valve can only regulate a process properly when its actual position follows the command from the control system. The Masoneilan SVI II AP is designed to manage this task through digital position control.
The SVI II AP receives a 4–20 mA setpoint and uses HART communication to exchange information with compatible configuration and maintenance tools. A microprocessor processes the control signal and adjusts the pneumatic output to move the actuator. The position sensor measures valve movement without requiring a mechanical shaft to pass into the main housing.
This non-contact sensing arrangement is one of the practical design features of the SVI II AP. It reduces the number of moving parts exposed inside the enclosure and supports installation on both linear and rotary pneumatic actuators.
The positioner also provides automatic stop detection and auto-tuning functions. These help establish operating parameters during commissioning, while allowing technicians to make further adjustments when the valve response needs to be refined.
For plants using conventional analog positioners, the SVI II AP can also be considered for retrofit projects. Its mounting arrangement and actuator compatibility should be checked before replacement.
| Parameter | Specification |
|---|---|
| Manufacturer | Masoneilan |
| Model | SVI II AP |
| Product Type | Digital Valve Positioner |
| Control Input | 4–20 mA, two-wire |
| Communication | HART, Revision 5 or 7 |
| Input Resistance | 450 Ω |
| Power Supply | Loop-powered from 4–20 mA signal |
| Minimum Current for Start-up | 3.2 mA |
| Actuator Type | Pneumatic, single-acting or double-acting |
| Valve Movement | Linear or rotary |
| Rotary Travel Range | 18°–140° |
| Reciprocating Travel Range | 6–64 mm standard; consult manufacturer for longer travel |
| Position Sensing | Non-contact position sensing |
| Local Interface | Optional LCD and three external push buttons |
| Housing | Copper-free aluminum; stainless steel option |
| Operating Temperature | -50°C to +85°C |
| Diagnostic Options | Standard and advanced diagnostics |
Specifications are for the SVI II AP product family. Options such as display, housing material, relay, diagnostic level and approvals depend on the ordered configuration.
The SVI II AP is used where pneumatic control valves need reliable position control and where maintenance teams need access to device-level information.
Typical installations include:
Oil and gas: Flow and pressure regulation in production, pipeline and gas-processing systems
Refining: Control valves in distillation, hydroprocessing and other process units
Petrochemical: Valve control in reactors, heat exchangers and process lines
Power generation: Steam, cooling-water and auxiliary process control
Chemical processing: Regulation of process fluids and utility systems
The valve does not reach its commanded position
This may be related to incorrect calibration, insufficient air supply, actuator limitations or mechanical resistance in the valve assembly. Check the actuator and air supply before changing positioner settings.
Valve movement is unstable or oscillates
An unsuitable tuning setting can contribute to excessive movement. The SVI II AP includes an auto-tune function, but the final response should be checked under actual operating conditions.
Position feedback is inconsistent
Inspect the position sensor alignment, mounting bracket and magnet assembly. Incorrect installation can affect the relationship between actual valve travel and the positioner reading.
HART communication cannot be established
Check the loop current, wiring, resistance and communicator configuration. The device must be installed in a compatible 4–20 mA loop.
Replacement selection should begin with the complete part number and the existing installation details.
Masoneilan SVI II AP: The preferred starting point when replacing an existing SVI II AP. Confirm relay type, housing, communication revision, diagnostic options and approvals.
Masoneilan SVI II AP High Flow: Consider only where the application requires the high-flow pneumatic configuration. It should not be treated as an automatic substitute for a standard-flow unit.
Masoneilan SVI3: May be evaluated for an upgrade or replacement project, subject to control-system, mounting, pneumatic and certification checks.
A replacement should be confirmed against the actuator, valve travel, air supply and hazardous-area requirements rather than selected by model name alone.
A positioner order often involves more than matching a model number. The relay configuration, actuator action, mounting arrangement and communication requirements all matter.
We support industrial buyers with:
Model and part-number identification
Sourcing of Masoneilan digital valve positioners
Configuration checks before quotation
Technical communication for replacement and maintenance orders
Coordination of international shipment
If you have an existing unit, its nameplate and installation details can help us check the requested configuration before the order is placed.
Availability depends on the SVI II AP configuration, including relay type, housing, display, diagnostics and certification requirements.
Please provide the complete model or part number and required quantity. We will check the available supply options and confirm the estimated lead time before order confirmation.
Export packing and international delivery can be arranged according to the destination and project schedule.
To help us identify the correct unit, please send:
Product: Masoneilan SVI II AP
Part Number / Full Type Code
Quantity
Relay Type: Single-acting / Double-acting / To be confirmed
Housing: Aluminum / Stainless Steel / To be confirmed
Display: With / Without
Communication: HART
Valve and Actuator Model
Destination Country
Required Delivery Date
Nameplate Photo: Recommended
We will use the supplied details to check the configuration and prepare a quotation.
Overall Rating
Rating Snapshot
The following is the distribution of all ratingsAll Reviews