| Communication Protocol | HART 7 |
|---|---|
| Maximum Output Pressure | 145 Psig |
| Process Control | Flow, Pressure, Temperature, Level |
| Input Signal | 4-20 MA DC, 24 VDC |
| Media Supply | Air Or Natural Gas |
| Signal Range | 4 To 20 MA · Two-wire Device, Reverse Polarity Protection · Minimum Span 4 MA |
|---|---|
| Hysteresis | ≤0.3 % |
| Sensitivity | ≤0.1 % |
| Valve Travel | 3.6 To 300 Mm |
| Direction Of Action | Reversible |
| Input Signal Options | 4-20 MA (analog), HART, FOUNDATION Fieldbus |
|---|---|
| Air Supply Pressure | 3-7 Bar |
| Protection Rating | IP66 |
| Accuracy | ≤ 0.25 % |
| Temperature Range | -52 °C To +85 °C (-62 °F To +185 °F) |
| Communication Port Protocol | HART, 4...20 MA Profibus FOUNDATION Fieldbus |
|---|---|
| Pneumatic Connection Type | 0.25 Inch 18 NPT G 1/4 |
| Input Pressure | 1.4...6 Bar |
| Stroke Range | 8...260 Mm |
| Maximum Hysteresis | 0.3 % |
| Communication Protocol | HART, 4-20mA Analog |
|---|---|
| Max Outlet Pressure | 101 Psig |
| Supply Media | Air, Non Corrosive Gas |
| Diagnostics | Yes |
| Packaging Details | Cardboard box/Wooden crate |
| Accuracy | +/- 0.5 Percent Full Span |
|---|---|
| Model Number | SVI II |
| Operating Temperature | -50°C To +85°C |
| Materials | Copper-free Aluminum Housing |
| Linearity | +/- 1 Percent Full Scale |
| Set Point | 4 To 20 MA |
|---|---|
| Valve Travel | 3.6 To 300 Mm |
| Opening Angle | 24 To 100° |
| Material | Aluminum |
| Packaging Details | Export wooden boxes for foreign trade, IPPC sterilized wooden boxes and plywood boxes for export customs inspection-free. Size: 60*30*40 (cm) |
| Process Control | Flow, Pressure, Temperature, Level |
|---|---|
| Diagnostics | Yes |
| Power Source | Local |
| Area Classification | Explosion Proof, Intrinsically Safe, FISCO, Type N, Flame Proof, Non-incendive For FM |
| Communication Protocol | 4-20 MA HART |
| Housing Material | Low Copper Chromated Aluminum (ASTM A360) |
|---|---|
| Protection Rating | IP66 / NEMA 4X |
| Weight | 2 Kg (4.5 Lb) |
| Input Power/Signal | 3.2-24 MA; Compliance: 9 VDC At 20 MA, 11 VDC At 4 MA |
| Optional Outputs | Two Solid-state Switches (1A/30 VDC); 4-20 MA Position Retransmit |
| Signal - Communication | HART 7 Over 4-20mA |
|---|---|
| Diagnostics | Positioner Diagnostics/Advanced Diagnostics/Online Valve Diagnostics |
| Construction / Materials | Copper-free Aluminum Housing/Optional 316SS Housing |
| Operating Temperature | -55°C To +85°C |
| Pneumatics Action | Single Acting, Fail Safe /Rotary And Linear |